| Site:
Naval Base Ventura County,
Point Mugu, CA (Swimming Pool) |
Period
Summary Statistics:
| |
|
Total |
Unit
# 315 |
Unit
#317 |
Start
Date |
|
-- |
1/18/2005
|
1/18/2005
|
| Thru
Date |
|
-- |
8/31/2005
|
8/31/2005 |
Hours
of Operation |
Hours |
8600 |
3977
|
4626 |
| kWh
Output |
kWh |
21513 |
10294
|
10858 |
Input
Fuel |
MMBTU |
297.2 |
147.1
|
150.2 |
| Electric
Efficiency |
% |
24.40% |
23.75%
|
25.07% |
Availability
|
% |
84.2% |
74.46%
|
92.58% |
| Capacity
Factor |
% |
42.3% |
39.45%
|
43.84% |
Unit#1
(System Number#SU01B000000315)
| Date |
Oper.
Hours |
Total
kWh |
Avg.
kW |
Capacity
Factor |
Availability |
Input
Fuel (MMBTU) |
Electric
Eff. |
| 08/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 09/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 10/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 11/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 12/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00% |
0.00% |
| 01/05 |
270.0 |
891.9 |
3.27 |
57.19% |
88% |
15.78 |
20.79% |
| 02/05 |
493.0 |
1271.6 |
2.58 |
37.85% |
73% |
17.8 |
24.42% |
03/05 |
216.0 |
541.7 |
2.51 |
14.56% |
29% |
7.4 |
24.96% |
| 04/05 |
113.0 |
282.6 |
2.50 |
7.85% |
16% |
4.0 |
23.64% |
05/05 |
744.0 |
1851.8 |
2.49 |
49.78% |
100% |
25.8 |
24.50% |
| 06/05 |
720 |
1833.3 |
2.55 |
50.93% |
100% |
26.0 |
24.06% |
07/05 |
717 |
1807.9 |
2.52 |
48.60% |
96.50% |
25.8 |
23.92% |
| 08/05 |
702 |
1810.6 |
2.58 |
48.67% |
94.49% |
25.8 |
23.96% |
| |
|
|
|
|
|
|
|
Unit#2
(System Number#SU01B000000317)
| Date |
Oper.
Hours |
Total
kWh |
Avg.
kW |
Capacity
Factor |
Availability |
Input
Fuel (MMBTU) |
Electric
Eff. |
| 08/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 09/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 10/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 11/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 12/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 01/05 |
270.8 |
677.2 |
2.50
|
40.31%
|
81%
|
8.58
|
26.95%
|
| 02/05 |
672.0 |
1670.3 |
2.49 |
49.71% |
100% |
21.5 |
26.52% |
03/05 |
491.5 |
1211.6 |
2.47 |
32.57% |
66.0% |
15.7 |
26.25% |
| 04/05 |
525.8 |
1131.5 |
2.15 |
31.43% |
73.0% |
15.7 |
24.63% |
05/05 |
744 |
1840.8 |
2.47 |
49.495% |
100% |
26.2 |
24.00% |
| 06/05 |
720 |
1658.0 |
2.30 |
46.06% |
100% |
23.4 |
24.14% |
07/05 |
699 |
1557.7 |
2.23 |
41.87% |
94.03% |
21.9 |
24.31% |
| 08/05 |
703 |
1616.5 |
2.30 |
43.46% |
94.49% |
23.1 |
23.86% |
| |
|
|
|
|
|
|
|
Average
kW = kWh ÷ Operating Hours
Availability = Operating
Hours ÷ Hours in Period
Capacity Factor =
Total kW Hours ÷ [Total Period Hours * Fuel Cell Rated kW]
Electrical Efficiency