Total |
Unit
# 252
|
| Start
Date |
|
-- |
2/26/2004
|
Thru
Date |
|
-- |
8/31/2005
|
Hours
of Operation |
Hours |
4462 |
4462
|
kWh
Output |
kWh |
10843.1 |
10843.1
|
Input
Fuel |
MMBTU
|
158.1 |
158.1
|
Electric
Efficiency |
% |
23.41% |
23.41%
|
Availability
|
% |
99.98% |
99.98%
|
Capacity
Factor |
% |
48.69% |
48.69% |
Unit#1
(System Number#SU01B000000252)
| Date |
Oper.
Hours |
Total
kWh |
Avg.
kW |
Capacity
Factor |
Availability |
Input
Fuel (MMBTU) |
Electric
Eff. |
| 08/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 09/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 10/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 11/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
12/04 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
01/05 |
0.0 |
0.0 |
0.00 |
0.00% |
0% |
0.00 |
0.00% |
| 02/05 |
48 |
118.63 |
2.47 |
49.43% |
100% |
1.74 |
23.2% |
03/05 |
744 |
1769.24 |
2.38 |
47.56% |
100% |
26.03 |
23.1% |
| 04/05 |
720 |
1781.78 |
2.47 |
49.49% |
100% |
25.25 |
24.0% |
05/05 |
743 |
1846.39 |
2.48 |
49.63% |
99.8% |
25.63 |
24.5% |
06/05 |
720 |
1721.6 |
2.39 |
47.82% |
100% |
25.5 |
23.08% |
07/05 |
744 |
1785.7 |
2.40 |
48.00% |
100% |
26.4 |
23.04% |
08/05 |
743 |
1819.7 |
2.45 |
48.92% |
99.97% |
27.3 |
22.74% |
| |
|
|
|
|
|
|
|
Average
kW = kWh ÷ Operating
Hours
Availability
= Operating Hours ÷ Hours in Period
Capacity Factor
= Total kW Hours ÷ [Total Period Hours * Fuel Cell
Rated kW]
Electrical Efficiency
= [kWh x 3413 Btu/kWh] ÷ [Input Fuel MMBTU x 1 million
Btu/MMBTU]
|