SITE:
POINT LOMA SUB BASE (SITE LAYOUT CLICK
HERE)
LOCATION:
SAN DIEGO
BUILDING
APPLICATION: 501 BEQ
CHP LOOPS WORK PLAN
Site
Description
San
Diego, CA was a chosen site for eight Plug Power GenSysTM
5CS- 5kW PEM fuel cells. They are distributed between two
bases. Point Loma Sub Base has three of the eight units. These
fuel cells reform natural gas into a hydrogen fuel source,
CO2 and water vapor. The GenSys 5kW fuel cells offers uninterruptible
power to a critical load in the event of grid disturbance,
but in this demonstration project the critical load is not
connected. They are only connected to the grid and set to
allow 2.5kW output from the fuel cell. This allows for a capacity
factor of about 50% due the fuel cell primarily operating
at half of its rated capacity. These fuel cell installations
also capitalize on a combined heat and power (CHP) utilizing
the fuel cells waste heat to be recovered to supplement an
existing hot water system. The sites were chosen based on
their CHP utilization.
| Cummulative
Operating Hrs |
11362.09
Hours |
Capacity
Factor |
47.04%
|
| Total
Electric Output |
28083.18
kWh |
Availability
|
95.05%
|
| Total
Input Fuel |
308.80
MMBTU |
Electrical
Efficiency |
25.88%
|
| |
|
|
|
Site
Layout
|